To enable and program the on-board triggers (Trigger 1 / Output 17 and Trigger 2 / Output 18) on a Honeywell Vista 21iP, use an alpha keypad to enter programming mode with [Installer Code] + 800. Next, use menu *79 to map the output as normally low, and menu *80 to set the specific trigger event (such as arming status or alarm activation).
Enter Programming and Map Triggers (*79)
- Enter your Installer Code followed by 800 on your alpha keypad (the default installer code is usually
4112). - Press
*79to enter the output mapping menu. - Enter
17(for Trigger 1) or18(for Trigger 2), then press*. - Set the initial state. Enter
1to make the output normally low (or0for default normally high), then press*. - Enter
00and press*when finished mapping outputs to exit*79.
Program Trigger Behavior (*80)
- Press
*80to enter output definition programming. - Enter a 2-digit rule number slot (e.g.,
01for your first rule) and press*. - Press
*past the summary screen, then select what activates the trigger: enter2(activated by zone type) and press*. - Enter the desired Zone Type number (for example,
21for Armed Away,20for Armed Stay, or33for a burglary alarm) and press*. - Select the partition (
0for any partition) and press*. - Choose the output action (e.g.,
2to stay closed while active) and press*. - Enter the output number (
17or18) and press*. - Enter
00to exit*80, then press*99to exit programming mode safely.