Program a module on a Fire-Lite ES-200X

To program a module on a Fire-Lite ES-200X fire alarm panel, use the built-in keypad with the master programming password or autoprogram the SLC loop.

Entering Programming Mode

  • Press the Menu button on the front panel.
  • Enter the Master Programming Password (default is 00000000) to enter user/master programming mode.

Auto-Programming (Learning New Devices)

  • View programming screen #1 on the LCD display.
  • Press 1 to select Self-programming / Autoprogram. The panel will poll the SLC loop and automatically register any connected, properly addressed modules.

Manual Point Programming

  • Navigate to the Point Program option in the programming menu.
  • Select the specific loop and module address number corresponding to the physical device.
  • Assign the appropriate device type (e.g., monitor module, relay, pull station) and configure parameters like zone assignment or custom labels.
  • Save and exit the programming menus to store the changes.

Note: For larger or more complex setups, configurations are typically done via a PC using FS-Tools Programming Software uploaded through a USB drive or cable.