This is a multi-criteria wireless smoke detector which employs advanced levels of detection and discrimination. This reduces common cooking nuisance alarms and allows faster detection to different types of fire conditions. It is intended for use with Control Panels that support 5800 series devices.
To remove the mounting bracket, turn the top of the detector 15 degrees counterclockwise and separate the mounting bracket and top cover.
ENROLLMENT
The smoke detector must be enrolled in the Control Panel before it can operate in the system. The 5800SMOKEV smoke/heat protection zone must be enrolled as Loop 1 and “Input Type” 3 (supervised RF).
If programmed, this smoke detector is capable of monitoring the additional conditions of Maintenance (transmitted as Loop 2), and Low Temperature (transmitted as Loop 3). Tamper is transmitted as Loop 4, but does not require programming. To take advantage of the value added features of Maintenance and Low Temperature, you must program each loop as a separate zone in the 5800 series wireless compatible panel.
1. Enter the Control’s Zone Programming mode.
2. Enter the zone number to be programmed.
3. Enter the applicable zone type when prompted.
- Loop 1 (Heat/Smoke) as a Fire zone (type 9 or 16)
- Loop 2 (High/Low Maintenance) as a 24-Hr. Trouble zone (type 19)
- Loop 3 (Freeze Warning Sensor) as a 24-Hr. Aux. zone (type 8)
4. When prompted, enter Input Type 03 (3 on some control panels) – Supervised RF Transmitter.
PROGRAM
Consult the Control Panel’s instructions to program the device in the system. This detector reports the following signals to the Control Panel:
- Smoke and Heat detection
- Smoke Alarm when smoke is detected
- Heat Alarm when temperature of 135° F (57° C) or greater
- Rate-of-Rise Alarm when temperature is >104° F (40° C) @ 15° F/minute (8.33° C/minute).
- Maintenance: Contaminated chamber that requires cleaning
- End-of-Life
- Base Tamper: It sends a tamper signal to the Control Panel when the smoke head is removed from its base.
- Supervision: The detector will transmit its status every 60-70 minutes.
TAMPER
When the detector is removed from its base, it sends a tamper signal to the Control Panel.

TESTING
The detector should be tested immediately after installation and at least once a year.
After enrolling, verify adequate signal strength by conducting a sensor test (see the Control Panel’s instructions) with the device in its intended mounting location. Adjust the device location and orientation as necessary.
Tests and testing methods
There is no specific Test Mode that needs to be initiated to test smoke, heat, or Rate-of-Rise. These can be applied to the detector at any time as a test.
• Test Button – When the Test Button is held down, the unit initiates a test on the smoke sensor, chamber, heat sensor, End-of- Life, and battery. If all tests pass, it sounds a normal alarm and sends alarm signal to the Control Panel. However, if one of these tests fails, it sends a trouble signal to the Control Panel and provides fail status on the yellow led and sounder. The Test Button is also used to silence or Hush the detector. To Hush the detector, press and release the large Test Button. Depending on how much smoke is still in the chamber determines if the Hush feature silences the detector and make it send an Alarm restore to the Control Panel. If there is too much smoke still in the chamber, it does not Hush nor send a restore to the Control Panel. When Hush is successful, the sounder comes back on after 10 minutes and a restore signal is still not sent provided there is still enough smoke in the chamber to be considered an alarm. Once the smoke level is below threshold in the chamber, Hush causes the sounder to remain off and the restore signal is sent.
• Smoke Entry Test (canned smoke*) – Can be done at any time. Once the chamber is clear, the sounder will stop, and it will send a restore signal to the Control Panel.
• Direct Heat Test (hair dryer 12” or further from the detector)
• 135° F fixed Heat Detection
• Rate-of-Rise >104° F (40° C) @ 15° F/minute (8.33° C/minute).

LEDS AND SOUNDER
The 5800SMOKEV has one bi-color (red and yellow) LED with an 85dB sounder. Refer to the following table below for operation of these features.

CLEANING
Recommended: To prevent unwanted alarms, notify the Central Station that the smoke detector system is undergoing maintenance before cleaning the detector. To clean the detector, carefully vacuum the side vents all the way around, then, wipe them with a clean damp cloth and dry thoroughly.
BATTERY REPLACEMENT
1. Twist the front cover counterclockwise 15 degrees and separate it from the mounting bracket.
2. Remove both batteries and wait 10 seconds, then insert two new recommended batteries: Panasonic CR123A.
3. Reattach the detector to the mounting plate.
