VISTA-128BPT/250BPT: System Commands

User Code Commands

Add A User Code = User Code + 8 + New User Number + New User’s Code
Change a Code = User Code + 8 + User Number + New User’s Code
Delete a User Code = Master Code + 8 + User Number to Be Deleted + Master code again
View User Capability = User’s Code + [*] + [*]
Set Real-Time Clock (Installer, Master Only) = Code + [#] + 63

Programming Commands

Site Initiated Download = User Code + [#] + 1.
Activate Communication Session with Compass via the Dialer = Installer Code + [#] + 1.
Direct-Wire Download Enable = User Code + [#] + 5.
Enter Program Mode = Installer Code + 8000.
Enter Interactive Program Mode = Installer Code + 8000 + [#] + 93
Exit Program Mode = *99 or *98.

Event Logging Commands

Event Log Display = Code + [#] + 60 (Installer or Master Only)
Event Log Print = Code + [#] + 61 (Installer or Master Only)
Clear Event Log = Code + [#] + 62 (Installer or Master Only)

Wireless System Commands

House ID Sniffer Mode = Code + [#] + 2 (Installer Only)
Transmitter ID Test = Code + [#] + 3 (Installer Only)
Go/No Go Test = Code + 5 (Test Key)

Additional Commands

Partition GOTO = User Code + [✳] + Partition Number 0-8.
GOTO Home Partition = User Code + [✳] + 0.

Panics
[✳] + 1 or A Key (Zone 995).
[✳] + [#] or B Key (Zone 999).
[#] + 3 or C Key (Zone 996).

View Downloaded Messages = Press 0 for 5 Seconds.
Display All Zone Descriptors = Press [✳] for 5 Seconds.

Output Device Control Commands

Activate Output Device as Programmed = User Code + [#] + 71.
Activate Output Device as Programmed = User Code + [#] + 72.
Activate Output Device Manually = User Code + [#] + 70.
Activate Output Device or System Event Instantly = User Code + [#] + 77.
Randomize Output Devices = User Code + [#] + 41
Randomize Output Devices Programmed with Activation Times Between 6 PM and 5 AM = User Code + [#] + 42.
De-activate Randomization = Enter the sequence used to activate randomization.

Scheduling Commands

Installer-Programmed Schedule Events = Installer Code + [#] + 80 (Installer or Master Only).
Temporary Schedule Editing = User Code + [#] + 81 (Installer, Master, Manager Only).
Extend Closing Window = User Code + [#] + 82 (Installer, Master, Manager Only).
End User Output Device Programming = User Code + [#] + 83.

Access Control Commands

Activate Access Relay for Current Partition = User Code + 0.
Request to Enter/Exit = User Code + [#] + 73.
Request to Enter/Exit at Access Point = User Code + [#] + 74 + Access Point Number.
Change Access Point State = User Code + [#] + 75 + Access Point + State.
Perform a Test of the VistaKey Module = Installer Code + [#] + 78.
Perform an Access Control Card Function = User Code + [#] + 79.

Master Code + # + 65

This option is only set via downloading. When enabled, downloaded and a Compass disconnect occurs, a 24-hour window for keypad programming will be allowed. However, once the 24-hour time limit expires, keypad programming will no longer be permitted unless a Master Code + # + 65 is entered or another Compass connection/disconnect occurs. Once this is done, keypad programming will be allowed, and upon exiting programming, the 24-window lockout cycle will begin again.

Was this article helpful?