Alarm Docs
  • Submit Article
  • Contact Us
  • About Us
  1. Home
  2. Fire Alarm
  3. MS-9200: Standard Relays
Searching...

Other Articles

  • DMP XF6: Accessory devices
  • Reset Alula radio/communicator
  • How to add a zone to a VISTA H3
  • DMP XF6: Programming requirements
  • DMP XF6: Compatibility
  • DMP XF6: Wire the panel
  • DMP XF6: Install the panel
  • DMP XF6: Specifications Summary
  • XF6: Operating Instructions
  • Radionics: D168 Module Installation
  • PROA7PLUS: Re-register the radio
  • Install piezo on Honeywell Vista 21
  • S2000 – How to enter programming
  • DMP: Version 263 Update
  • Qolsys IQ4: Latest firmware version
  • Napco GEM-P1632: Error codes
  • Honeywell VISTA-128BPT compatible devices
  • Honeywell Vista 128BPT: ECP Error
  • Updating firmware on an Alula cellular communicator
  • How to update NAPCO StarLink firmware
  • How to adjust thermostat from IQ Panel 5
  • Create a guest code on the Qolsys IQ5
  • Programming VISTA-21iP for internet-only
  • Program user code on DMP XR/XT panel
  • Program the on-board triggers on Vista 21

MS-9200: Standard Relays

The MS-9200 provides a set of Form-C alarm and Form-C trouble contacts rated for 2.0 amps @ 30 VDC (resistive). The panel also provides a Form-A supervisory contact rated for 2.0 amps @ 30 VDC (resistive).

Note that relay connections may be power-limited or nonpower-limited, provided that 0.25″ spacing is maintained between conductors of power-limited and nonpower-limited circuits.

Tagged: relayrelays
Was this article helpful?
Yes No
© Copyright 2026 - AlarmDocs.Com