Fire-Lite MS-5210UD: System Supervisory Condition Response

Program zones for Supervisory in applications where a waterflow sensing device has been employed and the wiring to the waterflow valve and/or a tamper switch is to be monitored. If the tamper switch has been activated (Normally Open contacts close), a supervisory alarm condition will occur.

When a supervisory condition occurs, the control panel will cause the following:

  • Blink the FACP supervisory LED (½ second On, ½ second Off)
  • Display the following message: SUXX (XX=Zone Number)
  • Communicate the supervisory condition to the Central Station
  • Store the ‘supervisory’ message in the History File
  • Pulse system piezo sounders (½ second On, ½ second Off)
  • Turn on appropriate zone relay output (ACM-8RF)
  • Turn on any system relays (main circuit board) programmed for supervisory activation
  • Output system supervisory message to printer
  • Terminate upload or download communications
  • Blink all remote annunciator general supervisory alarm LEDs (½ second On, ½ second Off)
  • Blink all remote annunciator zone supervisory alarm LEDs (½ second On, ½ second Off)